| General specifications | 
|---|
| Switching function | Normally open (NO) | 
| Output type | Two-wire | 
| Rated operating distance | 15 mm | 
| Installation | flush | 
| Output polarity | AC/DC | 
| Reduction factor rAl | 0.5 | 
| Reduction factor rCu | 0.45 | 
| Reduction factor r304 | 0.75 | 
| Nominal ratings | 
|---|
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | 
| Switching frequency | 30 Hz | 
| Hysteresis | 3 ... 15 typ. 5 % | 
| Reverse polarity protection | reverse polarity tolerant | 
| Short-circuit protection | yes | 
| Voltage drop | ≤ 8 V | 
| Operating current | 4 ... 500 mA AC/DC | 
| Off-state current | ≤ 0.8 mA | 
| Operating voltage indicator | LED, green | 
| Switching state indicator | LED, yellow | 
| Functional safety related parameters | 
|---|
| MTTFd | 1036 a | 
| Mission Time (TM) | 20 a | 
| Diagnostic Coverage (DC) | 0 % | 
| Approvals and certificates | 
|---|
| UL approval | cULus Listed, General Purpose | 
| CSA approval | cCSAus Listed, General Purpose | 
| CCC approval | Certified by China Compulsory Certification (CCC) | 
| Ambient conditions | 
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | 
| Mechanical specifications | 
|---|
| Connection type | cable PUR , 2 m | 
| Core cross-section | 0.5 mm2 | 
| Housing material | brass, nickel-plated | 
| Sensing face | PBT | 
| Housing diameter | 30 mm | 
| Degree of protection | IP67 |